Phoenix Contact 2810625 Current Measuring Transducer – MACX MCR-SL-CAC-5-I-UP
The Phoenix Contact MACX MCR-SL-CAC-5-I-UP is a DIN rail-mounted current measuring transducer designed to convert sinusoidal AC currents of 1 A or 5 A into a standard 0–20 mA or 4–20 mA analog signal. Ideal for energy monitoring, panel instrumentation, and control systems, this compact unit features DIP-switch configuration, 3-way electrical isolation, and integrated LED diagnostics.
Its wide supply range from 19.2 V to 253 V AC/DC makes it suitable for universal deployment in automation environments.
Technical Specifications
Model: MACX MCR-SL-CAC-5-I-UP
Part Number: Phoenix Contact 2810625
Product Type: Current Measuring Transducer
Input Current: 1 A AC or 5 A AC (configurable)
Output Signal: 0–20 mA or 4–20 mA (configurable via DIP switch)
Power Supply Range: 19.2 V AC/DC to 253 V AC/DC
Input Frequency Range: 45–65 Hz
Output Load: < 500 Ω (at 20 mA)
Max Output Current: 25 mA
Power Consumption: < 0.8 W (at 24 V DC)
Enclosure Rating: IP20
Mounting Type: DIN rail NS 35
Connection Method: Screw terminal
Dimensions (W × H × D): 22.5 × 104 × 114.5 mm
Weight: Approx. 120 g
Input Characteristics
- Input Current Ranges:
- 0–1 A AC
- 0–5 A AC
- Overload Protection:
- Continuous: 2 × IN
- 1-second Surge: 20 × IN
- Input Impedance: < 50 mΩ
- Voltage Isolation:
- Input/Output: 4 kV AC
- Output/Supply: 2 kV AC
- Curve Type: Sinusoidal
- Frequency Range: 50 Hz nominal (45–65 Hz accepted)
Output & Status Monitoring
- Signal Output:
- Configurable 0–20 mA or 4–20 mA
- Non-load Voltage: 15 V
- Ripple: < 10 mVPP
- Status LEDs:
- Green: Device operational
- Red: Error condition
- Step Response Time: ≤ 300 ms
- Transmission Accuracy: ≤ 0.5% of nominal range
- Temperature Drift: < 0.02 %/K
Mechanical & Environmental
- Housing Material: Polyamide PA (non-reinforced)
- Mounting Orientation: Vertical DIN rail
- Ambient Operating Temperature: –20°C to +65°C
- Storage Temperature: –40°C to +85°C
- Max Altitude: 2000 m
- Relative Humidity: 10–95% (non-condensing)
- Pollution Degree: 2
- Overvoltage Category: III
- Degree of Protection: IP20
Applications
Ideal For:
- Monitoring of AC current loops in industrial environments
- Energy metering and load tracking
- Integration into SCADA, PLC, and energy monitoring systems
- Use in control panels and switchgear with 1 A or 5 A CTs
Key Features & Benefits
✅ Flexible Configuration: Selectable input/output via DIP switches.
✅ Universal Supply: 19.2–253 V AC/DC compatibility.
✅ Reliable Isolation: 3-way electrical separation for safety and noise immunity.
✅ DIN Rail Slimline Design: Only 22.5 mm width for space-saving installs.
✅ Visual Diagnostics: LED indicators for operational and fault status.
📦 Available from Drive Outlet Megastore
The Phoenix Contact MACX MCR-SL-CAC- 5-I-UP transducer offers accurate current measurement and signal conditioning with high reliability and long-term stability.
Need assistance with configuration or current transformer selection? Contact our instrumentation specialists now.
Phoenix precision, Drive Outlet service — engineered to perform.

Reviews
There are no reviews yet.