Pepperl+Fuchs KFD2-SOT3-Ex2 Switch Amplifier (262108)
The KFD2-SOT3-Ex2 switch amplifier from Pepperl+Fuchs is a 2-channel isolated barrier that safely transfers digital signals from NAMUR sensors or dry contacts in hazardous areas to a safe control zone. It includes dual passive transistor outputs, line fault detection, and supports reversed mode operation via DIP switches. Designed for use in SIL 2 applications and optimized for Power Rail integration, it provides reliable signal transfer in compact form.
Technical Specifications
- Model: KFD2-SOT3-Ex2
- Type: Intrinsically Safe Switch Amplifier
- Input Type: NAMUR sensor or dry contact
- Output Type: 2 passive transistor outputs
- Channels: 2
- Mounting: 35 mm DIN rail (EN 60715)
Input Specifications
- Input Terminals: 1+, 2+, 3- and 4+, 5+, 6-
- Standard: EN 60947-5-6 (NAMUR)
- Open Circuit Voltage: Approx. 10 V DC
- Short-Circuit Current: Approx. 8 mA
- Switching Point: 1.2 … 2.1 mA
- Hysteresis: Approx. 0.2 mA
- Line Fault Detection: Break ≤ 0.1 mA, Short ≥ 6.5 mA
- Pulse/Pause Ratio: Min. 100 µs
Output Specifications
- Output Terminals: 7, 8 (Output I); 8, 9 (Output II)
- Rated Voltage: 30 V DC
- Rated Current: 100 mA (short-circuit protected)
- Signal Level: 1-signal: ≤ 3 V @ 100 mA; 0-signal: ≤ 10 µA off-state
- Response Time: ≤ 200 µs
Power & Configuration
- Supply Voltage: 19 … 30 V DC
- Power Source: Power Rail or terminals 14+, 15-
- Power Dissipation: ≤ 1.1 W
- Configuration: DIP switches
- Visual Indicators: LEDs (per NAMUR NE44)
Galvanic Isolation
- Input/Output: Reinforced insulation (300 Veff)
- Input/Power Supply: Reinforced insulation (300 Veff)
- Output/Power Supply: Basic insulation (300 Veff)
Environmental & Mechanical
- Operating Temperature: -20 … 60 °C
- Degree of Protection: IP20
- Connection: Screw terminals
- Dimensions: 20 x 119 x 115 mm (W x H x D)
- Weight: Approx. 150 g
Certifications & Safety
- Safety Integrity Level: SIL 2 (SC 3) per IEC/EN 61508
- ATEX Marking:
- II 3(1)G Ex nA [ia Ga] IIC T4 Gc
- II (1)D [Ex ia Da] IIIC
- I (M1) [Ex ia Ma] I
- IECEx Marking:
- Ex nA [ia Ga] IIC T4 Gc
- [Ex ia Da] IIIC
- [Ex ia Ma] I
- Certificates: EXA 16 ATEX 0016 X, IECEx EXA 16.0009X
- Max Safe Voltage (Um): 253 V AC (Input & Output)
Key Features & Benefits
✅ Dual NAMUR Inputs. Independently control two outputs from hazardous areas.
✅ Line Fault Detection. Break and short-circuit monitoring built-in.
✅ Short-Circuit Protection. 100 mA outputs with robust transistor drive.
✅ Compact & Durable. Slim 20 mm DIN rail housing.
✅ SIL 2 Compliant. Approved for functional safety-critical applications.
📦 Buy Pepperl+Fuchs KFD2-SOT3-Ex2 from Drive Outlet Megastore
Enhance your intrinsically safe control setup with the KFD2-SOT3-Ex2 – certified, reliable, and ready for dual-channel NAMUR input applications.
In stock now and available with 2–3 days delivery.

Reviews